SCM7B
Visit our website www.dataforth.com
81
Isolated Process Control Signal Conditioning Products
SCM7B
Specifications
Typical at 25°C and +24VDC
Output
Signal Range
(1)
4-20mA, 0-20mA 4-20mA
Effective Available Power
(1)
320mW *
Protection
Continuous 120Vrms max *
Transient ANSI/IEEE C37.90.1 *
Current Limit 32mA *
Input
Signal Range 1 to +5V, 0 to +10V 4-20mA
Bias Current ±1nA N/A
Resistance
Normal 10MΩ 270Ω
Power Off 30kΩ min >20kΩ
Overload 30kΩ min N/A
Protection ±35Vpeak (no damage) ±7.5Vpeak
Compliance N/A 35VDC max
CMV (Input-to-Output)
Continuous 1500Vrms *
Transient ANSI/IEEE C37.90.1 *
CMRR (50 or 60Hz) 110dB *
Accuracy
(2)
±0.03% Span typical, *
±0.1% Span max
Nonlinearity
(3)
±0.01% Span typical, *
±0.02% Span max
Stability (-40°C to +85°C)
Gain ±25ppm/°C ±50ppm/°C
Output Offset ±0.0035% Span/°C ±0.0045% Span/°C
Noise
Peak at 5MHz B/W 46µA *
RMS at 10Hz to 100kHz B/W 4µA *
Peak at 0.1Hz to 10Hz B/W 42nA *
Open Output Loop Detection
Response N/A Input Resistance
> 20kΩ
Detection Time N/A 5ms
Frequency and Time Response
Bandwidth, -3dB 100Hz *
NMR (-3dB at 100Hz) 80dB per decade above 100Hz *
Step Response, 90% Span 5ms *
Supply Voltage 18 to 35VDC *
Current
(1)
56mA *
Sensitivity ±0.0003%/%V
S
*
Mechanical Dimensions 2.13" x 1.705" x 0.605" max *
(h)(w)(d) 54.1mm x 43.3mm x 15.4mm max *
Environmental
Operating Temperature Range -40°C to +85°C *
ATEX Group II, Category 3 -20°C to +40°C *
Storage Temperature Range -40°C to +85°C *
Relative Humidity 0 to 95% noncondensing *
Emissions EN61000-6-4 ISM, Group 1 *
Radiated, Conducted Class A *
Immunity EN61000-6-2 ISM, Group 1 *
R F Performance A ±0.5% Span Error *
ESD, EFT, Surge, Voltage Dips Performance B *
Module SCM7B39-01,-02,-03 SCM7B39-04
Ordering Information
Model Input Range Output Range
NOTES:
* Same specification as SCM7B39-01, -02, -03
(1) Output Range and Supply Current specifications are based on maximum output load resistance. Maximum output
load resistance is calculated by P
E
/I
OUT
2
where P
E
is the Output Effective Available Power that guarantees output range,
accuracy, and linearity specifications. Output effective available power is independent of supply voltage.
(2) Accuracy includes the effects of repeatability, hysteresis, and linearity.
(3)
Nonlinearity is calculated using the best-fit straight line method.
SCM7B39-01 +1 to +5V 4 to 20mA
SCM7B39-02 0 to +10V 0 to 20mA
SCM7B39-03 0 to +10V 4 to 20mA
SCM7B39-04 4 to 20mA 4 to 20mA